All guides
Home → Guides → Septic tank drainage field in the UK: percolation test, size, layout and what is banned
Drainage field 🇬🇧 UK regulations

Septic tank drainage field in the UK: percolation test, size, layout and what is banned

A septic tank does only primary treatment, so its effluent must go to a drainage field or similar secondary treatment [1]. England allows a field where the percolation test gives an average Vp of 12–100 s/mm [2]; BS 6297 and Scotland use 15–100 [3]. The trench floor area is A = P × Vp × 0.25 m² [4]: for a four-bedroom house on soil with Vp 30 that is 45 m² (example calculation).

Updated 2026-09-29 · every regulation and price links to its source at the bottom of the page. A guide, not a construction design.

Why does a septic tank need a drainage field?

The tank only lets solids settle; the liquid leaving it still carries most of the pollution. The soil around the drainage field trenches finishes the job. That is why, in England, the only route to ground under the general binding rules is a drainage field after a septic tank or treatment plant: a well, a borehole or a rainwater soakaway installed after December 2007 does not qualify [5].

New fields are designed and built to BS 6297:2007 [6]. A site survey with percolation test typically costs £250–500 [7] and a new field £1,500–4,000 [8] (approximate, as of September 2026).

How do you check the groundwater level first?

Before the percolation test, dig a trial hole at least 1 m² in area and 2 m deep, or at least 1.5 m below the invert of the proposed distribution pipes. The groundwater table must not rise to within 1 m of that invert; if you dig in summer, allow for the higher winter level [9].

How do you do a percolation test?

The method in Approved Document H [10]:

Example calculation: water that takes 75 minutes (4,500 seconds) to drop 150 mm gives Vp = 4,500 ÷ 150 = 30 s/mm.

Which result allows a drainage field?

Approved Document H: “Drainage field disposal should only be used when percolation tests indicate average values of Vp of between 12 and 100” [2]. Faster soil lets poorly treated effluent reach groundwater; slower soil cannot absorb it.

Vp, s/mmEnglandScotland
Below 12No drainage field; use another form of secondary treatment [2]Up to 15: fast soil, subject to SEPA requirements [11]
12–15Allowed by Approved Document H, but BS 6297:2007 treats normal soil as over 15 [3]As above
15–100Drainage fieldStandard drainage field [11]
100–140No drainage field [2]Reed bed, constructed wetland or certified filter before the field [11]
Over 140No drainage fieldNo infiltration, or a mound filter system [11]
Since 23 July 2026 a drainage mound or engineered ground in England qualifies for the general binding rules only outside the floodplain, built to BS 6297:2007, and the engineered ground must reach a Vp of at least 15 [12].

How big should the drainage field be?

The trench floor area is A = P × Vp × 0.25 m², where P is the design population; after a sewage treatment plant use 0.20 instead of 0.25 [4]. Scotland uses the same formula [3]. P comes from British Water guidance: five people for a house with up to three bedrooms, plus one for each extra bedroom [13].

Example calculation, square metres of trench floor after a septic tank:

House (design population)Vp 20Vp 50Vp 80
Up to 3 bedrooms (5)25 m²62.5 m²100 m²
4 bedrooms (6)30 m²75 m²120 m²
5 bedrooms (7)35 m²87.5 m²140 m²

Size a septic system for your plot →

How is a drainage field laid out?

Distances in England: at least 15 m from any building, 10 m from a watercourse or permeable drain and 50 m from a groundwater abstraction point [15]. In Scotland: 5 m from a building and from the boundary, 10 m from watercourses, drains, roads and railways, and 50 m from any spring, well or borehole used for drinking water [16].

What cannot replace a drainage field?

In Scotland greywater from baths, showers, basins, sinks and washing machines may go to a separate infiltration field of A = P × Vp × 0.2 m² [19].

Design a house →

Frequently asked questions

What is a good percolation test result?

An average Vp between 12 and 100 s/mm allows a drainage field in England [2]; BS 6297 and Scotland use 15–100 [3].

How big a drainage field does a 3-bedroom house need?

Five people × Vp × 0.25. With Vp 40 that is 5 × 40 × 0.25 = 50 m² of trench floor (example calculation) [4].

Can I use an old soakaway for septic tank effluent?

No. A rainwater soakaway installed after December 2007, a well or a borehole does not meet the general binding rules [5].

Can I park or lay a patio over a drainage field?

No: no access roads, driveways or paving within the disposal area [17].

How far from a borehole must a drainage field be?

At least 50 m in England and in Scotland [15] [16].

Sources

  1. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.2, 1.15 (UK) · regulation · checked 2026-09-29 · source
  2. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.38 (UK) · regulation · checked 2026-09-29 · source
  3. gov.scot (UK) · regulation · checked 2026-09-29 · source
  4. Approved Document H (Building Regulations), H2, H2 1.34-1.37 (UK) · regulation · checked 2026-09-29 · source
  5. Environment Agency General Binding Rules: small sewage discharges (England), Rules that apply to all discharges — If you use a non-standard system (such as a well, borehole and soakaway) (UK) · prohibition · checked 2026-09-29 · source
  6. Environment Agency General Binding Rules: small sewage discharges (England), Make sure your treatment system meets the relevant British Standard (UK) · regulation · checked 2026-09-29 · source
  7. MyJobQuote — Septic Tank Installation Cost Guide (UK Prices 2026), Average cost; cost breakdown (UK) · price · checked 2026-09-29 · ✓ · source
  8. MyJobQuote — Septic Tank Installation Cost Guide (UK Prices 2026), Drainage field costs (UK) · price · checked 2026-09-29 · ✓ · source
  9. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.33 (UK) · regulation · checked 2026-09-29 · source
  10. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.34–1.37 (UK) · regulation · checked 2026-09-29 · source
  11. Scottish Building Standards Technical Handbook — Domestic (April 2026), 3.9.2 Design of infiltration fields (UK) · regulation · checked 2026-09-29 · ? · source
  12. Environment Agency General Binding Rules: small sewage discharges (England) (UK) · regulation · checked 2026-09-29 · source
  13. British Water Code of Practice — Flows and Loads 4 (2013) (UK) · recommendation · checked 2026-09-29 · source
  14. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.40–1.44 (UK) · regulation · checked 2026-09-29 · source
  15. Approved Document H (Building Regulations), H2, H2 (UK) · regulation · checked 2026-09-29 · source
  16. Scottish Building Standards Technical Handbook — Domestic (April 2026), 3.9.4–3.9.5 Location of infiltration fields (UK) · regulation · checked 2026-09-29 · ? · source
  17. Approved Document H (Building Regulations 2010, England), 2015 edition — H2, H2 para 1.28–1.30 (UK) · prohibition · checked 2026-09-29 · source
  18. Natural Resources Wales — Running and maintaining a septic tank or small sewage plant, Maintaining a septic tank; Maintenance records (UK) · recommendation · checked 2026-09-29 · ? · source
  19. Scottish Building Standards Technical Handbook — Domestic (April 2026), 3.9.3 Greywater disposal (UK) · regulation · checked 2026-09-29 · ? · source
  20. Environment Agency General Binding Rules: small sewage discharges (England), If you use a non-standard system (such as a well, borehole and soakaway) (UK) · recommendation · checked 2026-09-29 · source
  21. Environment Agency General Binding Rules: small sewage discharges (England), If you use a non-standard system — section G of the EA approach to groundwater protection (UK) · prohibition · checked 2026-09-29 · source
  22. Environment Agency General Binding Rules: small sewage discharges (England), Surface water — Use the correct treatment system (UK) · prohibition · checked 2026-09-29 · source
  23. Environment Agency General Binding Rules: small sewage discharges (England), Surface water — Make sure any partial drainage field is close enough to the watercourse (UK) · regulation · checked 2026-09-29 · source

🌐 🇺🇦 За нормами України · 🇵🇱 Według przepisów polskich · 🇫🇷 Selon la réglementation française · 🇺🇸 US rules · 🇩🇪 Nach deutschen Vorschriften